Polarities for Differential Pair Signals
(RS-422 and RS-485)
RS-485
Quick Guide - Just the Essentials on a Single Piece
of Paper
RS-485
Problem Solver - Trouble Shooting Guide Walks You
Step by Step
B&B Electronics labels the data lines
on RS-422 and RS-485 with an "A", for negative or "B" for
positive, to indicate the positive and negative relationship
between the two data lines. It is important to label the data
lines because this positive and negative relationship between
the lines must be maintained when connecting one device to
another.
Some manufacturers of RS-422/485 equipment
label the data lines on their devices with "+" or "-", Signal
and Inverted Signal, or an "A" and "B" that are opposite to
other converters or devices in the network. This can add confusion
when making connections or troubleshooting a network with
devices from different manufacturers. This application note
addresses some of these differences, show how they've come
about, and try to relate them to each other so that the system
designer can interconnect devices from different manufacturers.
What the Standards Say:
The RS-422 and RS-485 Standards define the two differential
signal lines as the "A" and "B" line. The signal state (0
or 1) is defined as the difference in voltage between the
two lines. At any receiver, a "1", (Idle, Mark, or Stop bit),
state is defined when the voltage on the "B" line is greater
than the voltage on the "A" line by at least 200 mV. A "0"
(Space or Start bit), state is defined when the voltage on
the "A" line is greater than the voltage on the "B" line by
at least 200mV. Shown in the equations below:
Va - Vb < -0.2V = "1"
Va - Vb > 0.2V = "0"
Where Va and Vb are the voltages on the "A" and "B" lines
respectively.
What Really Matters:
Regardless of the naming scheme used, the main consideration
in any RS-422/485 system is that the inversions remain constant
throughout the system. If we relate the above states to standard
TTL logic, when the "A" line is greater than the "B" line,
this would equal a 0 Volt TTL level. Conversely, when the
"B" line is greater than the "A" line, this would equal a
5 Volt TTL level. Figure 1 shows a typical asynchronous data
byte and it's corresponding signal levels in TTL, RS-232,
and RS-422/485.

Figure 1.
What Else We See:
"A" and "B" are opposite of what is shown
in the standard.
This has mainly arisen because manufacturers of RS-422 and
RS-485 interface IC's have always used the convention of labeling
the inverted pin of a differential transceiver as "B" and
the non-inverting pin as "A". Even differential transceivers
that pre-date or are not specifically designed for RS-422
or RS-485 use this naming scheme. Unfortunately, the "A" and
"B" pin labeled on the IC data sheet does not necessarily
have to correspond to the "A" and "B" in the RS-422/485 standard.
It depends on the logic on the TTL side of the device. Many
equipment manufacturers use the IC data sheet labeling and
transfer the signal names to the names for their interfaces.
The signals are labeled "+" and "-"
We don't know where this scheme originated, but it may have
started with an attempt to clear up the ambiguities of the
"A" and "B." "+" and "-" is certainly more descriptive than
"A" and "B" as to the relationship between the signals. In
almost all cases that we've seen, the "+" line will correspond
to the RS-422/485 "B" line and the "-" will correspond to
the "A" line.
The signals are labeled "Signal" and
"Signal*" or "Inverted Signal"
In this case the signal names used definitely correspond to
the inverting an non-inverting pins on the transceiver IC.
The "Signal line will almost always correspond to the "B"
line of the standard, and the "Signal*" or "Inverted Signal"
will correspond to the "A" line in the standard.
What B&B Does:
B&B tries to include the RS-422/485 specifications' naming
scheme on all of our products. Because of its common use,
most of our data sheets and product labels also include the
"+" and "-" naming scheme along with the "A" and "B".
What if I'm Unsure?
Reversing the two lines in the differential signal is by
far the most common initial error when connecting two pieces
of RS-422 or RS-485 equipment. The good news is that it won't
cause any damage to your equipment to try it the wrong way.
If you try it connected one way and are seeing garbled data,
reverse the leads and try again.
If this doesn't instill a level of confidence
you are comfortable with, or you have tried both combinations
with negative results, you can usually use a DC voltmeter
to determine which line is which.
- Measure the voltage across the two lines at the receiver
without the driver connected. On an RS-485 device the driver
and receiver are on the same pair.
- Note which signal line the positive lead of the voltmeter
is connected to.
- Is the reading positive or negative?
- If the reading is positive, the signal line going to
the positive lead of the voltmeter corresponds to the "B"
line of the RS-422/485 standards.
- If the reading is negative, the signal line going to
the positive lead of the voltmeter corresponds to the "A"
line of the RS-422/485 standards.
|