
How do I connect two FOSTCDR Fiber Converters
to Isolate and Extend RS-232? (RS-422/485)
The RS-232 connections depend on whether the RS-232 devices
are configured as (1) DTE or DCE, the wiring for normal interconnections
before adding the Converters, and (2) how many active signal
lines are required by the devices. You can use the FOSTCDR
(or FOSTC) if your RS-232 device is “3-wire” and
requires only Receive (Rx), Transmit (Tx) and Ground connections.
Some RS-232 devices will perform hardware handshaking using
RTS/CTS or DTR/DSR/CD, so the FOSTC or FOSTCDR cannot be used.
The 232FLST or 9PFLST may be suitable, directly supporting
RTS/CTS connections, or DTR/DSR may be remapped into RTS/CTS
pins using custom cable wiring. Check FAQ for those models.
See figure below: Set switch Sw #6 to OFF. Other switches
have no effect on RS-232 operation. If using one end as RS-232,
the other end as RS-422 or RS-485, the RS-232 side will match
either the left side or right side connection in the figures
which follow.
- The RS-232 device on the left side has DTE pinouts which
match a computer with DB9M connector. Pin #3 is output (Tx),
pin #2 is input (Rx), pin #5 is ground. See DTE figure for
DB-25 pinouts. Signal flow for DTE and DCE is opposite.
- The RS-232 device on the right side has DCE pinouts similar
to a modem, so pin #3 on the device is input (Tx), pin #2
is output (Rx), #5 is ground, note crossover. See DCE figure
for DB-25 pinouts.
How to identify which line should connect to Terminal D (Output)
from the RS-232 device:
Take a DC voltmeter, measure from the ground wire to each
of the other two RS-232 wires, while the RS-232 device is
powered up. Usually one lead has a minus (-) DC voltage, typically
between –11 volts and –3 volts. Whichever lead
has a minus voltage is the lead to connect to our Terminal
D. The other lead usually has nothing or noise relative to
ground. If neither lead has a minus (or positive) voltage
on it relative to ground, recheck for OPEN cable connections
to the RS-232 device or the device pinouts. If the device
can be configured multiple ways, make sure all the jumpers
and such are set to RS-232.
A few devices may use very low power RS-232 ports which switch
only between Ground and positive, so to identify which is
line is active, the device must be set to transmit, then connect
the ground wire to the FOSTCDR and one of the wires to D,
see if the TD indicator flashes. If not, try the other wire.
If the data request is coming from the other end, and all
that wiring is correct, and if it is being polled, the RD
indicator should be flashing. Some DC meters may show a slight
flicker of DC or AC voltage on a data line with changing data.


The RS-232 loopbacks are only needed if the software or devices
need them to operate, if the output is looped back and active,
the matching input will be active. On a host computer, software
may choose to ignore them if not used or may use them only
to verify a cable is connected.
The FOSTCDR (and FOSTC) keep the light in the fiber turned
on when no data is transmitted and the input signal is in
the MARK state. If light is lost or too low, the electrical
signals go to the SPACE state. The input signal turns the
light off/on in step with the data. The indicator for Transmit
indicates sending data out the fiber, Receive is data from
the fiber. If the Receive indicator is lighted when no fiber
is connected, no light is being received. To check, try the
other fiber into RX or use a fiber patch cable from TX to
RX.
How do I connect two FOSTCDR Fiber Converters to extend
and isolate RS-485 or RS-422 signals? (RS-232)
See the Connection figures for “2-Wire” RS-485
and “4-Wire” RS-485 or RS-422.

In 2-Wire RS-485 mode, the receiver and transmitter must
be connected together, and switches #7 and # 8 set to On.
Set the baud rate switches to match the baud rate of the data
so that data is not lost. Not all RS-485 devices are marked
correctly for Data (+) and (-), so if the slave devices don’t
respond after going through the fiber converts, try swapping
the wire pairs polarity to each converter. When there is no
light received from the fiber in, the receive indicator will
be On. You can interconnect or loop back the transmit fiber
on one unit to the receive input on the same unit to verity
the receive light goes out. If the transmit light is lighted
all the time without data, the polarity of the RS-485 is reversed,
or there is not enough bias, or termination loads on the RS-485
bus. Normal bias before termination is about 3.8 to 4.0 VDC,
Data (+) to (-). See our RS-422/485 Application note for more
information on biasing. Fiber data has Priority.

Set switch #7 to On for RS-485 transmit, to Off for RS-422
mode transmit. Set switch #8 to Off to enable the receiver.
See notes above if receive light is on, or if transmit light
is on. A faint red light can be seen in the transmit ST connector
when the fiber is removed.
|