Dataline Surge Protection:
Stop Fried Boards, Corrupted Data
Surges and spikes on datalines can fry your communications
boards and corrupt data. This article describes the operation,
installation and selection of what is probably the most common
method of data line protection. Surge Suppressors divert excess
energy away from the port being protected into a ground connection.
The operation of these devices relies on a high quality ground
connection in order to safely shunt away unwanted energy.
Surge Suppressor Operation
Shunting harmful currents to ground before they reach the
data port is the job of components such as Transient Voltage
Suppressors (TVS, often referred to by the trade name Tranzorbs),
Metal Oxide Varistors (MOV) or gas discharge tubes. These
devices all work by turning on at a set voltage. Once the
clamp voltage has been exceeded, the devices provide a low
impedance connection between terminals. These shunting devices
are most often installed from each data line to the local
earth ground, and should be selected to begin conducting current
at a voltage as close as possible above the system's normal
communications level. For RS-422 and RS-485 systems, the voltage
rating selected is typically 5 - 7 volts, in RS-232 systems
12 - 15 volt devices are appropriate. These devices typically
add some capacitive load to the data lines, similar to adding
additional cable to the system. This should be considered
when designing a system by reducing the total allowable line
length. Several hundred feet is usually an adequate figure
in RS-422 and RS-485 systems.
How Surge Protection Works - Illustration
What does a surge look like?
While transients may not always conform to industry specifications,
both the Institute of Electrical and Electronics Engineers
(IEEE) and the International Electrotechnical Commission (IEC)
have developed transient models for use in evaluating electrical
and electronic equipment for immunity to surges. These models
can offer some insight into the types of energy that must
be controlled to prevent system damage. Both IEC 1000-4-5:
1995 "Surge Immunity Test" and IEEE C62.41-1991 "IEEE Recommended
Practice on Surge Voltages in Low-Voltage AC Power Circuits"
define a "1.2/50µs - 8/20µs combination wave"
surge which has a 1.2 µs voltage risetime with a 50
µs decay across an open circuit. The specified current
waveform has an 8 µs rise time with a 20 µs decay
into a short circuit. Open circuit voltage levels from 1 to
6 kV are commonly used in both the positive and negative polarities,
although under some circumstances voltages as high as 20 kV
may be applied. Figures 1 and 2 illustrate the combination
wave characteristics. In addition, IEEE C62.41 also specifies
a 100 kHz "ring wave" test. The ring wave has a 0.5 µs
risetime and a decaying oscillation at 100 kHz with source
impedance of 12W as shown in Figure 3. Typical amplitudes
for the 100 kHz ring wave also range from 1 - 6 kV.

Figure 1. Combination Wave Voltage Waveform

Figure 2. Combination Wave Current Waveform

Figure 3. 100 kHz Ring Wave
Installation
Surge suppressors must be installed as close to the port
to be protected as possible, and must have an extremely low
impedance connection to the local earth ground of the unit
being protected. This ground connection is crucial for proper
operation, providing a shunt path for excess energy as well
as a ground reference at the same potential as the host. In
most cases, this means the ground connection should be made
from the surge suppressor directly to the chassis of the host
device.
The impedance of the ground connection is critical. The voltage
presented to the data port is equal to the clamping voltage
of the surge suppression device plus the voltage drop in the
suppressor's ground path to the node being protected. Any
voltage drop in the ground connection will effectively increase
the clamping voltage seen at the data port. Transient currents
can be very large, with magnitudes measured in thousands of
amps. At these current levels, the DC voltage drop (I X R)
can be very large. For example, 6 feet of 18AWG wire has approximately
0.039 ohms resistance. Although this initially appears to
be a good ground connection, calculating I X R with a 3000
amp transient yields a voltage of 117 volts across the ground
wire - enough to destroy any data port. To make matters worse,
at the frequencies illustrated in Figures 1-3, the inductance
of the ground wire causes an additional voltage drop that
can be much higher than the I X R voltage drop. To minimize
this voltage drop the ground connection should be made with
heavy gauge wire and kept as short as possible. If the cable
must be longer than one meter, braided cable intended for
grounding purposes must be used.
Selecting a Surge Suppression Device
Two basic types of surge suppression products are available
as illustrated in Figure 4. In either case, the system designer
should consider the clamping voltage of the unit as well as
its physical attributes, such as connector type and method
of making the grounding connection.

Figure 4. Surge Suppressor Schematics
Single Stage Devices
The most common device uses a single TVS or MOV for each
protected line. This type of unit is usually small and inexpensive.
If a proper ground connection is made, they should offer protection
against most transients. A disadvantage of this device is
that if a large transient damages one or more of the components
there often is no indication that the unit has failed, leaving
the node unprotected against future transients.
Three Stage Devices
More advanced units use three components on each protected
line to handle much larger surge currents and to provide internal
self protection, reducing the risk of undetected failures.
The first stage is a gas discharge tube; this stage can shunt
very large currents, but is slow reacting and requires a relatively
large voltage before conduction begins. The second stage is
series impedance; this stage limits the current flowing into
the final stage of the circuit. Finally, a TVS device clamps
at a voltage acceptable for the data port and maintains the
clamp until the gas discharge tube begins conduction.
Conclusion
Protecting a system against transients with surge suppression
requires attention to the selection as well as the installation
of the suppression device. Any surge suppressor can be rendered
ineffective if proper grounding techniques are not carefully
followed. Confronting these issues early in the system design
can reduce potentially time and money consuming problems before
they occur.
|